MEGGER EGIL 19093 Circuit Breaker Analyzer

MEGGER EGIL 19093 Circuit Breaker Analyzer

Rp. 365,000,000
NOTE
Harga dapat berubah sewaktu-waktu mengikuti perkembangan kurs rupiah terhadap mata uang asing lainnya sehingga sangat mungkin terjadi adanya perbedaan harga yang berlaku dengan harga yang tertera pada website kami.
The Egil is intended for use on circuit breakers with one contact per phase. EGIL incorporates features commonly found on more complex test systems, but is designed to be smaller, simpler to use and less expensive than other  Megger EGIL controlssimilar test sets. If the main contacts are equipped with parallel pre-insertion resistor contacts, the Megger Egil automatically records the difference between main and resistor contacts. Auxiliary contact timing as well as coil current traces are recorded.
 
Intended primarily for measuring travel (motion), the optional analog input channel finds many other uses as well. If this channel is not installed, all associated menu commands are hidden. It also comes with a USB interface for communication with a PC and the CABA Win™ Circuit Breaker Analysis Software.
 
It’s price makes it attractive to smaller utilities and it is an ideal supplementary product for maintenance departments at larger power companies and for testing contractors.
 
FEATURES
Suitable for testing timing and travel on all circuit breakers with single interrupter per phase.
Extremely easy-to-use and reliable.
Two separate timing channels for measurement of auxiliary contacts.
Analog measurement channels for travel transducers or general voltage/current measurements.
Static and dynamic resistance measurements along with the SDRM201 optional accessory.
 
TECHNICAL SPECIFICATIONS
Megger EGIL Specs:  
Operating temperature: 0°C to +50°C (32°F to +122°F).
Storage & transport: -40°C to +70°C (-40°F to +158°F).
CE Marking: EMC - 2004/108/EC. LVD - 2006/95/EC.
Mains voltage: 115 / 230 V AC (switchable), 50 / 60 Hz.
Power consumption: 100 VA (max).
Measurement time: 1 to 100 s.
Resolution: 0.1 to 10 ms.
Breaker operation Sequences: C, O, C-O, O-C, O-C-O.
Continuous current: 5 A.
Max current: 25 A during 300 ms, rest time 1 min.
Contact characteristics: Non bouncing, closing time max. 0.1 ms.
Make/Break capacity: 25 A, 250 V (AC or DC) per contact function.
Start breaker operation: By rotary switch.
Display: LCD.
Instrument dimensions: 360 x 210 x 190 mm (14.2” x 8.3” x 7.5”).
Weight: 6.3 kg (14 lbs). 10 kg (22 lbs) with accessories and transport case.
Megger Egil Warranty: 1 year.
Languages: English, German, French, Spanish, Swedish.
 
AVAILABLE MODELS
Ordering Information Order Code  
EGIL Basic Unit BM-19090
EGIL with USB port BM -19092
Egil with analog input channel and USB port (this page) BM -19093
Egil with SDRM option and USB port BM-19095